HXGN15-12 High Voltage Ring Main Unit

HXGN15-12 High Voltage Ring Main Unit

HXGN15-12 outdoor metal-clad ring main unit switchgear (intelligent type) applies to three phase AC system with rated voltage 12kv, rated frequency 5oHz, rated current 63oA and for ring network electricity supply and radiation terminal power supply that used as cable line sectionalizing, branch connection. It is equipped with sF6 gas insulating multiloop power unit and feeder terminal device. It has functions of remote signaling, telemetry, remote control and fault current detection. This device is mainly used as distribution automation system for city power supply load center and cable supply.
  • Free Samples
  • Quality Assurance
  • 24/7 Customer Service

Product Introduction

HXGN15-12 High voltage Ring Main unit

1. overview

HXGN15-12 outdoor metal-clad ring main unit switchgear (intelligent type) applies to three phase AC system with rated voltage 12kv, rated frequency 5oHz, rated current 63oA and for ring network electricity supply and radiation terminal power supply that used as cable line sectionalizing, branch connection. It is equipped with sF6 gas insulating multiloop power unit and feeder terminal device. It has functions of remote signaling, telemetry, remote control and fault current detection. This device is mainly used as distribution automation system for city power supply load center and cable supply.

2. Model Description

HXGN15-12 High Voltage Ring Main Unit

 

3. Environmental Requirements

Normal Operation Conditions

1. AItitude :≤ 2000m

2. Ambient temperature: -10.C ~ +40.C (temperature can be as Iow as -25.C during transportation and storage)

3. ReIative humidity: daiIy reIative humidity < 95% on average; monthIy reIative humidity < 90% on average

4. seismic scaIe of earthquake < 8

5. The switchgear is appIicabIe to category II contaminated environment.

SpeciaI Operation Conditions

If the switchgear wiII be used in conditions that exceed the normaI environmentaI conditions, users shaII negotiate with the manufacturer.

4. Technical Indicators of the switchgear

Item No.

Item

unit

VaIue

1

Rated voItage

KV

12

2

Rated current

A

Load break switch: 630

circuit breaker: 630,1250,1600,2000,2500,3150

3

Rated short circuit breaking current

KA

combination units: 50

circuit breaker: 20,25,31.5,40

4

Rated peak withstand current (peak vaIue)

KA

primary system: 50,63,80,100

5

4s Ratad short-time withstand current (vaIid vaIue)

KA

Load break switch: 20

6

Rated insuIating IeveI

1min power frequencY / ImpuIes withstand voItage

KV

42/75

7

Protection degree

 

IP4X

8

configuration of circuit breaker

 

ZN28 ZN63A(VS1) VD4 etc.

9

optionaI Ioad break switch

 

FLN36,SFL,SFG etc.

10

operating mechanism

 

spring mechanism

11

operationaI power suppIY

V

Dc: 110,220; Ac:110,220

12

outIine dimension(width depth height)

mm

375(500,800,1000) x 1000 x 1650(1800)

13

weight

Kg

500~1000

5. structure drawing

HXGN15-12 High Voltage Ring Main Unit